The Picard Maneuver@lemmy.world to hmmm@lemmy.world · 25 days agohmmmlemmy.worldexternal-linkmessage-square107fedilinkarrow-up1480arrow-down16
arrow-up1474arrow-down1external-linkhmmmlemmy.worldThe Picard Maneuver@lemmy.world to hmmm@lemmy.world · 25 days agomessage-square107fedilink
minus-squarekn33@lemmy.worldlinkfedilinkEnglisharrow-up1·25 days agoIn America, they always say that continuous loads should run at 80%. That’s why circuit breakers are specced at 15/20/30/40/50/60 amp but the EVSE is specced at 12/16/24/32/40/48 amp.
minus-squarepsmgx@lemmy.worldlinkfedilinkarrow-up2·25 days agoAye. US NEC says 80% is safe carrying capacity. There is an expectation there will be surges or dirty power that might take it a little
minus-squareabsGeekNZ@lemmy.nzlinkfedilinkEnglisharrow-up1·25 days agoThat is probably good practice. But your cable SHOULD be rated to run at 100% continuously, if it is not, then the rating is wrong.
In America, they always say that continuous loads should run at 80%. That’s why circuit breakers are specced at 15/20/30/40/50/60 amp but the EVSE is specced at 12/16/24/32/40/48 amp.
Aye. US NEC says 80% is safe carrying capacity. There is an expectation there will be surges or dirty power that might take it a little
That is probably good practice.
But your cable SHOULD be rated to run at 100% continuously, if it is not, then the rating is wrong.